Request a price
A meeting room can move from empty to fully occupied within minutes. A ventilation schedule based only on office opening hours cannot describe every change in demand. Carbon dioxide measurements can provide additional information because people exhale CO₂. In suitable occupied spaces, the resulting trend can help an operator assess whether outdoor-air ventilation is keeping pace with use.

A CO₂ sensor is not a complete indoor-air-quality monitor. It does not directly measure every pollutant, and a single reading cannot prove that a room is safe or unsafe in every respect. Sensor placement also matters: a device next to an open window or close to someone’s face may give an unrepresentative picture. Readings are more useful when recorded with occupancy and the ventilation conditions at the time.

Numerical thresholds require context. The UK Health and Safety Executive states that CO₂ levels consistently above 1500 ppm in an occupied room indicate poor ventilation and should prompt action. This is guidance from a British authority, not a Czech statutory limit or a universal boundary between safe and unsafe air. A value of 1000 ppm represents a volume fraction of 0.1%; it does not mean that oxygen has fallen to a dangerous concentration. Occupancy patterns, outdoor CO₂, activities and other pollution sources all affect interpretation. The sensor is an operational indicator, not a replacement for a ventilation assessment.

Airflow calculations help translate a control objective into equipment requirements. As an illustrative design assumption, 10 people each receiving 10 litres per second of outdoor air require 100 litres per second, equivalent to 360 m³/h. In a room of 180 m³, that corresponds to 2 air changes per hour. These values are a worked example, not a prescribed rate for every Czech meeting room. The required design airflow depends on the applicable project requirements, occupancy and activities. It also matters whether the quoted airflow is genuinely outdoor air rather than air recirculated within the building.

Placement and response time influence what the controller sees. A sensor close to a person’s exhaled breath can register a local plume rather than the mixed room condition. A sensor beside a supply diffuser can be biased in the opposite direction. Follow the manufacturer’s placement instructions and use an appropriate reference when checking measurements. Consider a hypothetical sensor uncertainty of ±50 ppm: readings of 980 and 1020 ppm do not reliably demonstrate a meaningful change on their own. That uncertainty is an example, not a specification for all CO₂ devices. Trends and repeated observations are usually more informative than small instantaneous differences.

A control sequence should define the minimum airflow, how ventilation rises with demand, its upper limit and what happens when the signal is stale or implausible. Avoid rapid switching around a single threshold by using suitable filtering, hysteresis or continuous modulation. The particular settings require commissioning; excessive smoothing can hide a fast rise in occupancy. Verify that a commanded fan increase actually delivers more outdoor air and does not merely change an icon. Finally, log both comfort complaints and ventilation response during representative meetings. This links the CO₂ signal to a measurable building service instead of treating the displayed number as the final outcome.

For an illustrative meeting room, the building team could compare the CO₂ trend during several ordinary meetings, noting the number of people and the fan settings. If the readings repeatedly rise as occupancy increases, the next step is to investigate ventilation delivery and control. A sudden flat line or implausible jump should also prompt a check of the sensor and its communications. Automation needs trustworthy measurements before it can make useful decisions.

Where the system supports demand-based ventilation, a designer can use the signal within an appropriate control strategy while preserving the required minimum ventilation. Noise, draughts and the response to a failed sensor must also be considered. The goal is a room that responds sensibly to changing use. Clear trends and tested controls are more valuable than a prominent display whose numbers have no agreed meaning or follow-up action.
Articles